Assessment of the 3410 Building Filtered Exhaust Stack Sampling Probe Location | |
Glissmeyer, John A.; Flaherty, Julia E. | |
2010-07-16 | |
出版年 | 2010 |
语种 | 英语 |
国家 | 美国 |
领域 | 地球科学 |
英文摘要 | Pacific Northwest National Laboratory performed several tests in the exhaust air discharge from the new 3410 Building Filtered Exhaust Stack to determine whether the air sampling probe for emissions monitoring for radionuclides is acceptable. The method followed involved adopting the results of a previously performed test series from a system with a similar configuration, followed by several tests on the actual system to verify the applicability of the previously performed tests. The qualification criteria for these types of stacks include metrics concerning 1) uniformity of air velocity, 2) sufficiently small flow angle with respect to the axis of the duct, 3) uniformity of tracer gas concentration, and 4) uniformity tracer particle concentration. |
英文关键词 | Exhaust stack sampling |
URL | 查看原文 |
来源平台 | US Department of Energy (DOE) |
引用统计 | |
文献类型 | 科技报告 |
条目标识符 | http://119.78.100.173/C666/handle/2XK7JSWQ/4762 |
专题 | 地球科学 |
推荐引用方式 GB/T 7714 | Glissmeyer, John A.,Flaherty, Julia E.. Assessment of the 3410 Building Filtered Exhaust Stack Sampling Probe Location,2010. |